AC Power, Power Factor & Wattless Current

Deconstruct alternating current electrical power into true active power ($P$), reactive power ($Q$), and apparent power ($S$). Investigate the role of phase angle ($\phi$) on the instantaneous power waveform $p(t) = v(t)i(t)$, visualize the dynamic complex power triangle, examine the physical nature of wattless current ($\phi = 90^\circ$), and perform industrial power factor correction using shunt capacitor banks.

🎯

3-Minute Investigation

Step 1 of 3
🎯 Active Mission: 1. Qualitative Observation (Tap to expand)
Mode 1 · Instantaneous Power Product Mode 1: Power Waveform Decomposition Active
Action: Plot V(t) = V_0*sin(omega*t) and I(t) = I_0*sin(omega*t - phi). Multiply to get p(t) = V(t)*I(t).
Observe: Instantaneous power oscillates at twice the line frequency (2*omega).
⏱ ~45s

Investigation Mode

AC Circuit & Load Parameters

230 V
50.0 Hz
30.0 Ω
127.3 mH

Simulation Playback & Speed

1.00×

Power Factor & Phase Presets

Physical Principles & Relations

In an AC circuit with impedance $Z$ and phase difference $\phi$, instantaneous power is $p(t) = v(t)i(t) = V_{\text{rms}} I_{\text{rms}} \cos\phi\,(1 - \cos 2\omega t) - V_{\text{rms}} I_{\text{rms}} \sin\phi\,\sin 2\omega t$. Over a full cycle, average active power is $P = V_{\text{rms}} I_{\text{rms}} \cos\phi$. When $\phi = 90^\circ$ ($\cos\phi = 0$), power oscillates with net average zero: the current is completely wattless. The ratio $\cos\phi = \frac{P}{S} = \frac{R}{Z}$ is the power factor.

cos φ: 0.600
Phase φ: 53.1°
|
P (True): 634.8 W
Q (Reactive): 846.4 VAR
Voltage Phasor ($\mathbf{V}$)
Current Phasor ($\mathbf{I}$)
Active Component ($I\cos\phi$)
Wattless Component ($I\sin\phi$)
Interactive 2D Visualizer • Dynamic Phasors, Circuit Current Beads & Power Decomposition
Active Power (P) 634.8 W
Reactive Power (Q) 846.4 VAR
Apparent Power (S) 1058.0 VA
Power Factor (cos φ) 0.600 (Lag)
Total RMS Current (I) 4.60 A
Instantaneous Power Decomposition • $p(t) = v(t) \cdot i(t)$